Prohledejte časté dotazy
How to turn off the backlight after a period of Inactivity on HMIST6/HMISTM6?
Issue:
Need assistance on how to turn off the backlight after inactivity
Product Line:
HMIST6, HMISTM6, EcoStruxure Operator Terminal Expert
Resolution:
To turn off the backlight on an HMIST6/HMISTM6 programmed with EcoStuxure Operator Terminal Expert, we first need to use the following system variable.
Preferences.BacklightOff : If you set this property ON, the back light of the touch panel turns off.
(valid for HMIGTU Series Premium Box, HMIST6 Series, HMISTM6 Series, and HMISTO Series)
Using the following global script, the backlight will turn off after 2 minutes of Inactivity.
Publikováno pro:Schneider Electric Česká republika
Zjistěte více
Řada:
Zjistěte více
Řada: