{}

Naše značky

Impact-Company-Logo-English Black-01-177x54

Vítejte na internetových stránkách společnosti Schneider Electric

Vítejte na našich internetových stránkách.
Prohledejte časté dotazy
PowerChute cannot register with Network Management Card/s and report a security certificate rejection.
Issue:
PowerChute cannot register with all Network Management Cards due to the rejection of the security certificate.

Product:
PowerChute Network Shutdown v5

Environment:
All support OS

Cause:
The Common Name (CN) values on the Network Management Cards SSL certificate CN value may be set to “.” (Period) by default on new NMCs.

To view the Network Management Card (NMC) security information, log into the Network Management Card and go to Configuration > Network > Web > SSL Certificate > Validate certificate.
SSL Certificate

Solution:
Use the Network Management Card Security Wizard to create and upload a new SSL certificate or generate a new self-signed certificate on the Network Management Card. In the Network Management Card UI, navigate to Configuration > Network > Web > SSL Certificate and select the option to remove the existing certificate. This will reboot the NMC and generate a new self-signed certificate with the CN value updated to use the Network Management Cards IP address or hostname.
remove SSL certificate

Schneider Electric Česká republika

Zjistěte více
Řada:
Užitečné články
Zjistěte více
Řada: