How to clean Heatcraft-Larkin Refrigeration condensers
Issue:
This document describes how to clean Heatcraft-Larkin Refrigeration condensers.

Product line:
Heatcraft Condensers, LNE, FCB, KH1,SCS, LNH,

Environment:
All Product models, all serial numbers.

Cause:
Install, Repair


Resolution:


Maintenance

Air cooled condensing units require a minimum of maintenance. The unit coil will require a periodic cleaning and this can be accomplished by a brush, vacuum cleaner, pressurized airstream or a commercially available coil cleaning foam. All of the condenser fan motors have sealed ball bearings. The only acceptable service to these bearings is replacement.

Cleaning Instructions

Heatcraft recommends that the finned surface of this unit be cleaned approximately every six (6) months; more frequent cleaning may be required if extreme conditions cause clogging or fouling of air passages through the finned surface.  Calgon Corporation's CalClean 41352 (or equal) should be acceptable for cleaning this unit. CalClean should be applied liberally to entering air and leaving air surfaces of the finned area in accordance with the label directions.

CAUTION: Under no circumstances should this unit be cleaned with an acid-based cleaner.


Reference Heatcraft-Larkin Refrigeration Products Remote Air Cooled Condensers Manual. Bulletin H-IM-73A June 2000 Part Number 90800801

Schneider Electric Deutschland

Anlage(n)
Heatcraft-Larkin Condenser Cleaning Requirements rev. 20111121.doc [823.5 KB]
How to clean Heatcraft-Larkin Refrigeration condensers
Issue:
This document describes how to clean Heatcraft-Larkin Refrigeration condensers.
 
Product line:
Heatcraft Condensers, LNE, FCB, KH1,SCS, LNH,
 
Environment:
All Product models, all serial numbers.
 
Cause:
Install, Repair


Resolution:
 
 
Maintenance
 
Air cooled condensing units require a minimum of maintenance. The unit coil will require a periodic cleaning and this can be accomplished by a brush, vacuum cleaner, pressurized airstream or a commercially available coil cleaning foam. All of the condenser fan motors have sealed ball bearings. The only acceptable service to these bearings is replacement.
 
Cleaning Instructions

Heatcraft recommends that the finned surface of this unit be cleaned approximately every six (6) months; more frequent cleaning may be required if extreme conditions cause clogging or fouling of air passages through the finned surface.  Calgon Corporation's CalClean 41352 (or equal) should be acceptable for cleaning this unit. CalClean should be applied liberally to entering air and leaving air surfaces of the finned area in accordance with the label directions.
 
CAUTION: Under no circumstances should this unit be cleaned with an acid-based cleaner.


Reference Heatcraft-Larkin Refrigeration Products Remote Air Cooled Condensers Manual.  Bulletin H-IM-73A June 2000 Part Number 90800801
 

Schneider Electric Deutschland

Anlage(n)
Heatcraft-Larkin Condenser Cleaning Requirements rev. 20111121.doc [823.5 KB]
Weitere Produktinformationen
Bereich:
Weitere Produktinformationen
Bereich:
Weitere Produktinformationen
Bereich:
Weitere Produktinformationen
Bereich:

FAQ-Nutzungshinweis

Bitte lesen Sie sich die Bedingungen für die FAQ genau durch. Sie müssen den Bedingungen zustimmen, bevor Sie mit der Suche beginnen können.

Die in den FAQs aufgeführten Antworten dienen als Hilfestellung und Orientierung. Es besteht kein Anspruch auf Vollständigkeit und Aktualität. Sie ersetzen nicht die AGBs, die Technischen Dokumentationen, die Gebrauchsanweisungen, die Sicherheitshinweise und die anerkannten Regeln der Technik.

move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.