Where to configure the DNP map for the ADVC controller within WSOS?

In order to configure the DNP map one must be able to locate it. Click Display > Switchgear Communications > Protocols > DNP3 > DNP3 Point Configuration > Click Configure Map. This will allow you to configure the active map for the switchgear.