Vores varemærker

Impact-Company-Logo-English Black-01-177x54

Velkommen til Schneider Electrics website

Velkommen til vores website

Søg i ofte stillede spørgsmål

What is the pinout to the RS485 cable needed to connect an M340 to a Unity Quantum RJ45 modbus port?

Note: If the cable is 10 feet or longer a 120 ohm resistor will be needed across pins 1 and 2 on the Quantum side as well as pins 4 and 5 on the M340 side.