{}

Vores varemærker

Impact-Company-Logo-English Black-01-177x54

Velkommen til Schneider Electrics website

Velkommen til vores website

Søg i ofte stillede spørgsmål

Pin-out for VX003 PC cable for RS232 port of VAMP 200 series

Issue:
Trying to connect to the VAMP 200 series through the RS232 port fails.

Product Line:
VAMP 255, VAMP 257,  VAMP 259, VAMP 200 series, VX003

Environment:
Connecting to VAMP set to configure settings.

Cause:
The RS232 port configuration is not a standard RS232 port.

Resolution:
Image 1

Schneider Electric Danmark

Se mere
Produkt:
VX003-3
Område:
Vamp 200 Series
Se mere
Produkt:
VX003-3
Område:
Vamp 200 Series