"PID feedback warning" on an ATV630
It is due to wrong limits for PID feedback monitoring.  If PFAH warning is displayed, it means that PID feedback has reached high threshold PAH [PID feedback high threshold].  Additionally if relay output has been assigned to PID feedback warning, it would be activated as well.  See extracted pages to fix high PID feedback warning. Increase PAH or lower PAL in order to always have PID feedback in this area PAL-PAH.

Schneider Electric Danmark

Bilag
Extracted 3 pages from ATV600_Programming_Manual_EN_EAV64318_05.pdf [378.59 KB]