Why doesn't SoMove Software show all assigned inputs under the Operate Tab, Input/Output terminals?
Issue:
Why doesn't SoMove Software show all assigned inputs under the Operate Tab, Input/Output terminals?

Product Line:
Altivar Machines, SoMove Software

Environment:
All models and serial numbers

Cause:
Programming

Resolution:
Per Level 3 - There is a limitation on SoMove, we see only LI1 and LI2 logic input, no LI3 to LI6.
The limitation is to avoid SoMove Modbus overload which can cause SoMove untimely disconnection.