{}

Vores varemærker

Impact-Company-Logo-English Black-01-177x54

Velkommen til Schneider Electrics website

Velkommen til vores website

Søg i ofte stillede spørgsmål

What is the method of phase imbalance detection and tripping in TeSys Giga OLR?

Tripping signal shall be sent by phase imbalance protection when detecting imbalance ratio is above 40%. And phase imbalance trip time is 5s(with tolerance ± 20%).
The definitions of phase imbalance ratio and average current according to Annex T T.5.5 IEC60947-1.

Schneider Electric Danmark

Se mere
Område:
TeSys Giga protection relays
Se mere
Område:
TeSys Giga protection relays