{}

Nos marques

Bienvenue sur le site Web de Schneider Electric

Bienvenue sur notre site Web.

Consulter notre FAQ

Video: How to Shutdown your Silcon UPS

Issue:
How to Shutdown your Silcon UPS

Product line:
Silcon DP300E

Environment:
All Product models, all serial numbers

Cause:
Shutdown Support

Resolution:
First step is to put the UPS into bypass



Hit the # Key and then Press "C" to change the option to yes



Press the # key again to save change.
The UPS is now in static bypass.

H3 LED will light indicating it is safe to operate Q3
Turn the Q3 switch on



H2 LED will light indicating it is safe to operate Q2
Turn the Q2 switch Off



Open the front door of the UPS and Press the Red button (acoustic alarm will sound for 30 seconds)
Open all battery breakers (or fuses)
Turn off the Q1 switch
Your UPS is now off

The following video demonstrates this procedure:

Schneider Electric Algeria

En savoir plus
Gamme :
En savoir plus
Gamme :