{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

This FAQ has been written for NEAL (North East Africa and Levant) region. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.

What is the procedures for selection of a surge arrestor ?

In our surge protection range we have three types of Surge Protection Devices as below :

a) Type 1 surge arrestor

> The Type 1 surge arrester is recommended for electrical installations in the service sector and industrial buildings
protected by a lightning conductor or by a meshed cage.
> It protects electrical installations against direct lightning strikes.
> It is used to conduct the direct lightning current, propagating from the earth conductor to the network conductors.
> It must be installed with an upstream disconnection device, such as a fuse or circuit breaker, whose breaking capacity
must be at least equal to the maximum prospective short-circuit current at the installation point.
> The Type 1 range of surge arresters meets the normative withstand capability of current wave type
10/350 μs.
> It is suitable for use with TT, TN-S, TN-C and 230 V IT earthing connection systems (neutral point connection).


b) Type 2 surge arrestor

> Type 2 surge arresters are installed downstream of type 1 lightning arresters in main distribution boards or sub-distribution boards.
> Type 2 surge arresters are tested with a 8/20 μs current wave.
> Discharges currents from indirect lightning strikes, inductive, conductive over voltages and switching transients.



c) Type 3 Surge arrestor

> The type 3 is for sensitive equipments.
> It corresponds to the secondary protection in our type 2 surge arresters if Up of incoming surge arrester > 1,5kV
or/and the distance between the incoming surge arrester and loads > 30m.
> These surge arresters ensures secondary protection of loads to be protected and is placed in cascade with the incoming
surge arresters.
> Type 3 surge arresters are tested with a 12/50 μs and 8/20 μs combined wave.

Please also find the link below for selection of surge arrester:-
https://www.se.com/products/in/en/1600-din-rail-modular-devices/1615-acti-9-surge-protection-devices-spds/7562-acti-9-iprd/

Schneider Electric Egypt and North East Africa

Explore more
Range:
Acti9 iPRD1, PRD1SurgeArrest EssentialSurgeArrest Performance
Explore more
Range:
Acti9 iPRD1, PRD1SurgeArrest EssentialSurgeArrest Performance
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.