{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

This FAQ has been written for NEAL (North East Africa and Levant) region. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.

How to monitor the ground fault current ( Ig ) and log the fault history using NSX with Micrologic2,5,6 or 7 ?

Please download the latest version of RCU Software which has the required features of Monitoring the current / voltage and trip histories etc..( See attached screenshots ). You can also export the files in excel format for the event history or logs:

https://www.se.com/products/ww/en/4200-power-circuit-breakers-switches/4230-molded-case-circuit-breaker/1887-compact-nsx-630a/?xtmc=Compact%2520NSX&xtcr=4

The indication of fault is visible on the micrologic display.
For example, tripped by ground fault protection (µlogic 6), on the micrologic display, a up-arrow is pointing to "Ig" , and the message displayed should be "trip".

Schneider Electric Egypt and North East Africa

Attachment(s)

RCU screenshots.pngRCU screenshots.png [265.81 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: