How to monitor the ground fault current ( Ig ) and log the fault history using NSX with Micrologic2,5,6 or 7 ?

Please download the latest version of RCU Software which has the required features of Monitoring the current / voltage and trip histories etc..( See attached screenshots ). You can also export the files in excel format for the event history or logs:

https://www.se.com/products/ww/en/4200-power-circuit-breakers-switches/4230-molded-case-circuit-breaker/1887-compact-nsx-630a/?xtmc=Compact%2520NSX&xtcr=4

The indication of fault is visible on the micrologic display.
For example, tripped by ground fault protection (µlogic 6), on the micrologic display, a up-arrow is pointing to "Ig" , and the message displayed should be "trip".