{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
This FAQ has been written for NEAL (North East Africa and Levant) region. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
How to disconnect the capacitor banks in Varset in case of switching on the Generator engine ?
Inside the Varset ,there is an input on terminal blocks 1 and 2 used for disconnecting the banks once the generator is switched on.

It is required to connect a normally closed contact between point 1 and 2,which will be opened when the generator starts and remains closed once generator stops.

The opening of contact between these two points cuts the power on regulator,and consequently disconnect the capacitor banks.



Schneider Electric Egypt and North East Africa

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: