{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

This FAQ has been written for NEAL (North East Africa and Levant) region. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.

Can we use a low voltage current transformer for a medium voltage application?

If the CT will be installed directly on medium voltage busbars, accordingly it must have an insulation level at least equal to that of the system/cubicle. However, if install a toroidal CT will be installed on the medium voltage cable (which is already insulated), in this case the CT can be a low voltage type (e.g. insulated 0.72kV).

Schneider Electric Egypt and North East Africa

Explore more
Range:
MV Indoor Current TransformerMV Outdoor Current Transformer
Explore more
Range:
MV Indoor Current TransformerMV Outdoor Current Transformer
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.