Search FAQs
This FAQ has been written for NEAL (North East Africa and Levant) region. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
Can we use a low power current transformer for a medium voltage application?
If the CT will be installed directly on medium voltage busbars, accordingly it must have an insulation level at least equal to that of the system/cubicle. However, if install a toroidal CT will be installed on the medium voltage cable (which is already insulated), in this case the CT can be a low voltage type (e.g. insulated 0.72kV).
Released for:Schneider Electric Egypt and North East Africa
Explore more
Range:
Explore more
Range: