Please advice if we can make mechanical interlock by cable for 3 sources (Transformer + Generaor-1 + Generator-2) for NS630b MCCBs and only one of them will be ON at each time.
Kindly be informed that the mechanical interlocking by cables between 3 devices is possible only for NW only,not NS breaker,( as per source changeover catalog ref.LVPED211022EN page A-11)

Consequently,in order to have a mechanical interlock by cables for 3 devices associated with ATS function,you will be obliged to change the NS breakers to NW.

In this case,the interlock by cable for 3 Masterpact NWs 1 out of 3 can be done in two ways as given below


a) 3 sources, only 1 device closed, fixed or drawout devices >> ordering code 48610 >> Instruction sheet 51156126AA-03.pdf

b) 2 normal, 1 replacement source, fixed or drawout devices >> 48608 >> 51156124AA-03.pdf

Please find attached the instruction sheets in each case for more details about the references used and the installation steps.

Schneider Electric Egypt and North East Africa

Attachment(s)
Interlocking 3 sources- 51156126AA-03.pdf [2.61 MB]
This FAQ has been written for NEAL (North East Africa and Levant) region. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
Please advice if we can make mechanical interlock by cable for 3 sources (Transformer + Generaor-1 + Generator-2) for NS630b MCCBs and only one of them will be ON at each time.
Kindly be informed that the mechanical interlocking by cables between 3 devices is possible only for NW only,not NS breaker,( as per source changeover catalog ref.LVPED211022EN page A-11)

Consequently,in order to have a mechanical interlock by cables for 3 devices associated with ATS function,you will be obliged to change the NS breakers to NW.

In this case,the interlock by cable for 3 Masterpact NWs 1 out of 3 can be done in two ways as given below


a) 3 sources, only 1 device closed, fixed or drawout devices >> ordering code 48610 >> Instruction sheet 51156126AA-03.pdf

b) 2 normal, 1 replacement source, fixed or drawout devices >> 48608 >> 51156124AA-03.pdf

Please find attached the instruction sheets in each case for more details about the references used and the installation steps.

 

Schneider Electric Egypt and North East Africa

Attachment(s)
Interlocking 3 sources- 51156126AA-03.pdf [2.61 MB]
Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.