{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
This FAQ has been written for NEAL (North East Africa and Levant) region. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
What is the switch on current (inrush current) of TRIHAL 500 kVA 11000/415 V Dyn 11 transformer?
A "precise" value of the inrush peak current depends on exact transformer data (rating plate information, impedance, etc.).
In attached pages, tabulated data given for liquid-filled & dry type transformers by France-Transfo (including Trihal which is dry type).

Example (for 500kVA Trihal transformer):
Peak inrush current = 10 times the transformer r.m.s rated current;
For 500kVA MV/LV transformer fed at MV side with 11kV, rated current = approximately 26.25A
The peak inrush current to be 262.5A with a decay time constant of approximately 0.25s.

Schneider Electric Egypt and North East Africa

Attachment(s)
Transformer inrush current.pdf [719.28 KB]
Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: