{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

This FAQ has been written for NEAL (North East Africa and Levant) region. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.

What are the authorized losses levels for transformers in EcoDesign regulation EU 548-2014?

For Oil Distribution and Dry-type transformers (≤ 3150 kVA):
  • Losses levels to be applied (reference of MV ≤ 24 kV and LV ≤ 1.1 kV).
  • ODT and CRT not covered by reference transformers (additional losses allowed compared to standard losses ranges):
  • Medium power and power transformers: Level of Peak Efficiency (Mix of load losses and no load losses) for transformers > 3150 kVA (limited to 10 MVA 36 kV for Dry-type Transformers)
- No losses levels imposed but minimum PEI (Peak Efficiency Index)
- PEI corresponds to:
- the maximum efficiency of the transformer
- Ratio between the no load losses and losses

The values given are Maximal value; no more tolerances on design considered:

Schneider Electric Egypt and North East Africa

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: