Contactor Selection table for DC current switching?
Guide for selection of contactor for DC application is in Attachment1.
E.g. for switching of 35A at 220VDC in utilization category DC-1 to DC-5 can be used contactor LC1D32 with 3 poles connected in series.
E.g. for switching of 35A at 220VDC in utilization category DC-1 to DC-5 can be used contactor LC1D32 with 3 poles connected in series.