Lighting up of the LED (flashing) and display of the MITOP FAULT alarm indicate that the VIP has
detected a fault in the Mitop trip unit connection circuit. In this case, the VIP does not go into the fail-safe
position and remains operational.
The VIP remains operational. Check the wired connection between the VIP and the Mitop trip unit.