Do we use the full function test kit FFTK for testing MTZ breaker?
No, we use Ecostruxure Power Commission (previously named Ecoreach) which proposes an "Automatic Trip Curve Test” to ensure that the protection functions are working correctly and are ready for operational values. Whereas FFTK is for NW/NT/NS range only.
Released for:Schneider Electric Egypt and North East Africa