Cannot access the PowerChute Business Edition version 10.0.2 Agent web interface.
Issue:
Cannot access the PowerChute Business Edition version 10.0.2 Agent web interface. This may arise after upgrading from version 10.0.1 or a clean install. Also, you may see Windows Event ID 1067, and in the pcbe.log found in C:/Progarm Files (x86)/APC/PowerChute Business Edition/agent/log, you will see "Unable to load permanent storage m11.cfg.  If this file is corrupted, you may need to re-install".

Product:
PowerChute Business Edition version 10.0.2 Agent

Environment:
All supported Windows OS

Cause:
Security changes made to Agent 10.0.2

Solution:
Uninstall PowerChute Business Edition 10.0.2 and install PowerChute Serial Shutdown, available at
https://www.se.com/ww/en/product-range/137943580-powerchute-serial-shutdown

Schneider Electric Egypt and North East Africa

Cannot access the PowerChute Business Edition version 10.0.2 Agent web interface.
Issue: 
Cannot access the PowerChute Business Edition version 10.0.2 Agent web interface. This may arise after upgrading from version 10.0.1 or a clean install. Also, you may see Windows Event ID 1067, and in the pcbe.log found in C:/Progarm Files (x86)/APC/PowerChute Business Edition/agent/log, you will see "Unable to load permanent storage m11.cfg.  If this file is corrupted, you may need to re-install".

Product:
PowerChute Business Edition version 10.0.2 Agent

Environment:
All supported Windows OS

Cause:
Security changes made to Agent 10.0.2

Solution:
Uninstall PowerChute Business Edition 10.0.2 and install PowerChute Serial Shutdown, available at
https://www.se.com/ww/en/product-range/137943580-powerchute-serial-shutdown

Schneider Electric Egypt and North East Africa

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.