Which devices need to be installed externally on the EVlink Home charger?
The EVlink Home charger must be protected at least by an overcurrent circuit breaker plus a minimum 30mA earth leakage Type A protection according to IEC 62851-1 and IEC 60364-7-722
Depending on your product, Mx or MNx auxiliary protection is also mandatory in some countries (refer to the user manuel included in the packaging).