How to change parameter of BMED581020 PLC (IEC 61499)
Where is PLC parameter: Open Logical Device
![logical device M580D logical device M580D](https://ckm-content.se.com/ckmContent/servlet/servlet.ImageServer?id=0158V00000CW67eQAD&oid=00DA0000000abSmMAI)
Modification of parameter: Select OVERWRITE on “Deploy Setting” by example
![PLC parameter M580D PLC parameter M580D](https://ckm-content.se.com/ckmContent/servlet/servlet.ImageServer?id=0158V00000CW67fQAD&oid=00DA0000000abSmMAI)
By default, “Auto start after deploy” is False
![PLC parameter M580D PLC parameter M580D](https://ckm-content.se.com/ckmContent/servlet/servlet.ImageServer?id=0158V00000CW67gQAD&oid=00DA0000000abSmMAI)
After deploy your PLC will be in “Stop” mode.
![Deploy false parameter M580D Deploy false parameter M580D](https://ckm-content.se.com/ckmContent/servlet/servlet.ImageServer?id=0158V00000CW67hQAD&oid=00DA0000000abSmMAI)
Change “Auto start after deploy” parameter is True
![change parameter true M580D change parameter true M580D](https://ckm-content.se.com/ckmContent/servlet/servlet.ImageServer?id=0158V00000CW67iQAD&oid=00DA0000000abSmMAI)
SAVE and BUILD
Now need to send this parameter in PLC.
Deploy Device Configuration + Deploy and restart
![deploy device configuration M580D deploy device configuration M580D](https://ckm-content.se.com/ckmContent/servlet/servlet.ImageServer?id=0158V00000CW67jQAD&oid=00DA0000000abSmMAI)
![Deploy and restart Deploy and restart](https://ckm-content.se.com/ckmContent/servlet/servlet.ImageServer?id=0158V00000CW67kQAD&oid=00DA0000000abSmMAI)
Now when you deploy your application PLC is in “RUN” mode.
![after deploy RUN after deploy RUN](https://ckm-content.se.com/ckmContent/servlet/servlet.ImageServer?id=0158V00000CW67lQAD&oid=00DA0000000abSmMAI)
Product Line
EAE 22.0, BMED581020, IEC 61499, PLC parameter
Environment
Windows, EcoStruxure Automation Expert 22.0
Modification of parameter: Select OVERWRITE on “Deploy Setting” by example
By default, “Auto start after deploy” is False
After deploy your PLC will be in “Stop” mode.
Change “Auto start after deploy” parameter is True
SAVE and BUILD
Now need to send this parameter in PLC.
Deploy Device Configuration + Deploy and restart
Now when you deploy your application PLC is in “RUN” mode.
Product Line
EAE 22.0, BMED581020, IEC 61499, PLC parameter
Environment
Windows, EcoStruxure Automation Expert 22.0
Released for:Schneider Electric Egypt and North East Africa