Issue
During the configuring of the Database Options settings for PQDIF Exporter, upon clicking the 'Test Settings' button the database connection fails and gives the following message:
"Test Database Connection Settings
Database connection failed.
Cannot open database "ION_Data_test" requested by the login.
The login failed.
Login failed for user 'Report'."
Here is a screenshot:
Product Line
ION Enterprise 5.x, 6.x
StruxureWare Power Monitoring (SPM) 7.0.1
Power Monitoring Expert (PME) 7.2.x and 8.x
Environment
PQDIF Exporter Configuration
Cause
The PQDIF Exporter configuration is defined with a non-existent or incorrect database, and throws this error when attempting to connect to it.
Resolution
*Warning: Take backups of any files prior to modifying them. Ensure the backups are in a location that will not be overwritten (i.e. the Desktop).
For Database*
The database configuration information is stored in a .xml configuration file. This file is named PQDIFExporterConfig.xml and can be located in the <InstallDirectory>\Power Monitoring Expert\config\exporters\PQDIF\config folder.
(e.g.. D:\Program Files (x86)\Schneider Electric\Power Monitoring Expert\config\exporters\PQDIF\config\PQDIFExporterConfig.xml)
Edit this file and locate the line containing the DatabaseConnection information.
Locate the non-existent or incorrect database name within this line and modify it to reflect the correct database name.
Save and close the file.
Note: Ensure the PQDIF Exporter Configuration UI is closed before you edit the PQDIFExporterConfig.xml file.
Publicado para: Schneider Electric España
Issue
During the configuring of the Database Options settings for PQDIF Exporter, upon clicking the 'Test Settings' button the database connection fails and gives the following message:
"Test Database Connection Settings
Database connection failed.
Cannot open database "ION_Data_test" requested by the login.
The login failed.
Login failed for user 'Report'."
Here is a screenshot:
Product Line
ION Enterprise 5.x, 6.x
StruxureWare Power Monitoring (SPM) 7.0.1
Power Monitoring Expert (PME) 7.2.x and 8.x
Environment
PQDIF Exporter Configuration
Cause
The PQDIF Exporter configuration is defined with a non-existent or incorrect database, and throws this error when attempting to connect to it.
Resolution
*Warning: Take backups of any files prior to modifying them. Ensure the backups are in a location that will not be overwritten (i.e. the Desktop).
For Database*
The database configuration information is stored in a .xml configuration file. This file is named PQDIFExporterConfig.xml and can be located in the <InstallDirectory>\Power Monitoring Expert\config\exporters\PQDIF\config folder.
(e.g.. D:\Program Files (x86)\Schneider Electric\Power Monitoring Expert\config\exporters\PQDIF\config\PQDIFExporterConfig.xml)
Edit this file and locate the line containing the DatabaseConnection information.
Locate the non-existent or incorrect database name within this line and modify it to reflect the correct database name.
Save and close the file.
Note: Ensure the PQDIF Exporter Configuration UI is closed before you edit the PQDIFExporterConfig.xml file.
Publicado para: Schneider Electric España




¿Necesitas ayuda?
Empieza aquí
Encuentra respuestas ahora. Busca una solución por ti mismo, o ponte en contacto con uno de nuestros expertos.
Contacta con el servicio de asistencia
Ponte en contacto con nuestro equipo de atención al cliente para recibir información, soporte técnico, asistencia para reclamaciones y mucho más.
¿Dónde comprar?
Encuentra fácilmente el distribuidor de Schneider Electric más cercano a tu ubicación.
Buscar preguntas frecuentes
Obtén las respuestas que necesitas examinando las preguntas frecuentes (FAQ) relacionadas con los temas.
Contacto con el servicio de ventas
Comienza tu consulta de ventas on-line y un experto se pondrá en contacto contigo.