How does a MiCOM P63x relay calculate Idiff and Irestrain
Issue
The user would like to calculate the Idiff (differential current) and Ires (restrain current) given the injection currents and matching factors
Product Line
Micom P63x transformer differential relay
Environment
Calculating MiCOM settings
Resolution
The formula below is used by the relay to calculate the Idiff and Irestrain:
![Calculation of the differential and restraining currents Calculation of the differential and restraining currents](https://ckm-content.se.com/ckmContent/servlet/servlet.ImageServer?id=0151H000008zqfCQAQ&oid=00DA0000000abSm)
To simplify the equations, assume that the Zero-sequence current filtering is disabled :
![Zero-sequence current filtering Zero-sequence current filtering](https://ckm-content.se.com/ckmContent/servlet/servlet.ImageServer?id=0151H000008zqS6QAI&oid=00DA0000000abSm)
Where Kam,a and Kam,b are the amplitude matching factors calculated by the relay based on Iref/Inom on side a and side b, respectively. Refer to the differential protection section in the manual for more information.
Example:
I,a,sec = 10 A I,nom,secondary= 5 Amps Kam,a= 2.76
I,b,sec = 5 A (180 deg) Kam,b= 1.32
![Formula for example Formula for example](https://ckm-content.se.com/ckmContent/servlet/servlet.ImageServer?id=0151H000008zqRwQAI&oid=00DA0000000abSm)
Iref is calculated based reference power and the nominal voltage on side a and b.
The user would like to calculate the Idiff (differential current) and Ires (restrain current) given the injection currents and matching factors
Product Line
Micom P63x transformer differential relay
Environment
Calculating MiCOM settings
Resolution
The formula below is used by the relay to calculate the Idiff and Irestrain:
To simplify the equations, assume that the Zero-sequence current filtering is disabled :
Where Kam,a and Kam,b are the amplitude matching factors calculated by the relay based on Iref/Inom on side a and side b, respectively. Refer to the differential protection section in the manual for more information.
Example:
I,a,sec = 10 A I,nom,secondary= 5 Amps Kam,a= 2.76
I,b,sec = 5 A (180 deg) Kam,b= 1.32
Iref is calculated based reference power and the nominal voltage on side a and b.