{}

Nuestras marcas

Impact-Company-Logo-English Black-01-177x54

Web de Schneider Electric España

Bienvenido a nuestra web

Preguntas frecuentes de búsqueda

Contactors fail to pass incoming inspection, contacts do not close.

Contactors should be tested under load, not with a digital meter. This is true even for devices that are in service.

See the attached paper.

Schneider Electric España

Documentos adjuntos

Ohmic verification of power contacts.docxOhmic verification of power contacts.docx [77.42 KB]
Explorar más
Rango:
Lighting ContactorsTeSys K contactorsType S Multipole Lighting ContactorTeSys Deca contactorsTeSys F
Explorar más
Rango:
Lighting ContactorsTeSys K contactorsType S Multipole Lighting ContactorTeSys Deca contactorsTeSys F