Contactors fail to pass incoming inspection, contacts do not close.

Contactors should be tested under load, not with a digital meter. This is true even for devices that are in service.

See the attached paper.

Schneider Electric España

Documentos adjuntos

Ohmic verification of power contacts.docxOhmic verification of power contacts.docx [77.42 KB]