When the 4.10 firmware is applied to the M580 CPU, first the 3.99 intermediate firmware must be applied.
Applying the 3.99 firmware will set the PLC back to the default MAC-based IP address. This will cause EADM or Unity Loader to appear to fail because the connection will time out due to the changed IP.
In addition, once the v4.10 firmware is loaded with the EADM tool, the same connection time-out condition failure will happen again because the IP will change back to what was loaded in the Control Expert project.
This issue does not occur when using USB connection.
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Publicado para: Schneider Electric España
When the 4.10 firmware is applied to the M580 CPU, first the 3.99 intermediate firmware must be applied.
Applying the 3.99 firmware will set the PLC back to the default MAC-based IP address. This will cause EADM or Unity Loader to appear to fail because the connection will time out due to the changed IP.
In addition, once the v4.10 firmware is loaded with the EADM tool, the same connection time-out condition failure will happen again because the IP will change back to what was loaded in the Control Expert project.
This issue does not occur when using USB connection.
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Publicado para: Schneider Electric España








¿Necesitas ayuda?
Empieza aquí
Encuentra respuestas ahora. Busca una solución por ti mismo, o ponte en contacto con uno de nuestros expertos.
Contacta con el servicio de asistencia
Ponte en contacto con nuestro equipo de atención al cliente para recibir información, soporte técnico, asistencia para reclamaciones y mucho más.
¿Dónde comprar?
Encuentra fácilmente el distribuidor de Schneider Electric más cercano a tu ubicación.
Buscar preguntas frecuentes
Obtén las respuestas que necesitas examinando las preguntas frecuentes (FAQ) relacionadas con los temas.
Contacto con el servicio de ventas
Comienza tu consulta de ventas on-line y un experto se pondrá en contacto contigo.