How to remove an RS modem from Easergy builder configuration
- Backup configuration
- Make sure no RS modem declared in slot1 or 2 in RTU modem list
- Delete the corresponding com channel in the Configuration
While Updating the configuration select, Below Option.
Send the configuration to the T300
- Make sure no RS modem declared in slot1 or 2 in RTU modem list
- Delete the corresponding com channel in the Configuration
While Updating the configuration select, Below Option.
Send the configuration to the T300