{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

Factory default settings for Micrologic trip units 5.2, 5.3, 6.2, 6.3 electronic trip units on Powerpact H, J, and L frame breakers.

Issue:
Factory default settings for Micrologic trip units 5.2, 5.3, 6.2, 6.3 electronic trip units on Powerpact H, J, and L frame breakers.

Product Line:
Circuit Breakers

Environment:
Powerpact H, J and L with Micrologic trip units

Cause:
Discovery of factory default settings

Resolution:

Factory Default settings for 5.x and 6.x:
Ir = 1.0 x In
tr = 2 seconds

Isd = 6 x Ir
tsd =  Off, 0 seconds

Ii = 1.5 x In

For 6.2:
Ig = .3 x In
tg = Off, 0 seconds

For 6.3
Ig = .2 x In
tg = Off, 0 seconds

Schneider Electric Hong Kong

Explore more
Range:
PowerPact H-Frame Molded Case Circuit BreakersPowerPact J-Frame Molded Case Circuit BreakersPowerPact L Frame Molded Case Circuit Breaker
Explore more
Range:
PowerPact H-Frame Molded Case Circuit BreakersPowerPact J-Frame Molded Case Circuit BreakersPowerPact L Frame Molded Case Circuit Breaker
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.