{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
How can all 8 channels of a BMXART0814 module be used to read thermocouples without the ABE7CPA412 block for cold junction compensation?

Issue

Can the BMXART0814 module be used without the ABE7CPA412 and maintain use of all 8 channels for Thermocouple operation?

Product Line

Modicon M340, Modicon M580, X80 IO.

Resolution

Yes. Using a 2-wire PT100 RTD wired to channel 4 on terminals EX+ and EX-. This will allow all 8 channels of the BMXART0814 to be used for thermocouple operation as configured and with a single  CJC from Channel 4. Channel 4 will have the 2-wire RTD on EX+ and EX- and the TC on MS+ and MS-.

Schneider Electric Hong Kong

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: