{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

What are the tripping times of the SM6 range switchgear?

For SM6 switches (IM, PM or QM type cubicle):

The average response times depend on the type of operating mechanism used with the switch:
  • 1 to 2 seconds on closing and opening for a motorised CIT operating mechanism
  • 5 to 7 seconds on closing and 25 to 35 ms on opening for a motorized CPI operating mechanism
  • 45 to 55 ms on closing
  • 25 to 35 ms on opening for a motorized CI2 operating mechanism after setting.

The switch can only break a current corresponding to its nominal current, i.e. 400 A or 630 A.
The circuit breaker can break a short-circuit current up to 12.5 kA.
For SM6 circuit breakers (DM1A, D or W type cubicle): after setting the operating mechanism, the average response times of the SF1 circuit breakers are: 70 ms for closing and 50 to 60 ms for opening.

Schneider Electric Hong Kong

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: