{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
Unable to configure GOOSE inputs for Vamp protection relays
Issue: Unable to configure GOOSE inputs for Vamp protection relays

Resolution: To be able to configure the GOOSE inputs for a VAMP relay you must select the Edition 2 Extensions check box when building the ICD file for the VAMP protection relay from VAMPset. This is what enables the GOOSE input configuration for the ICD file within VAMP SCD Editor.

Schneider Electric Hong Kong

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: