{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
What is the maximum customer cable size that can be connected per phase to ACB (MTZ/NT/NW) in BlokSeT?
In new BlokSeT catalogue, we have mentioned the maximum cable size that can be connected per phase of MTZ/NT/NW Masterpact. The cable includes both Copper and Aluminum cables.

For Example, for Side Connection, MTZ2/NW25 breaker, We can connect 2 x 300mm2 copper cables per phase.

Schneider Electric Hong Kong

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: