How to add VMware vCenter Server and/or ESXi host security certificate to PowerChute Network Shutdown keystore manually.
Issue:
Would like to add a VMware vCenter Server and/or ESXi host SSL certificate to the PowerChute Network Shutdown keystore.

Produce:
PowerChute Network Shutdown v4.x 5.x

Environment:
VMware ESXi 7.x, 8.x
VMware vCenter Server 7.x, 8.x

Cause:
Manually addition of the VMware SSL certificates to the PowerChute-keystore required.

Solution:
See the attached PDFs.

Add VMware vCenter Security Cert to PowerChute-keystore Manually.pdf
Add Vmware ESXi Host Security Certificate to PowerChute-keystore Manually.pdf

Schneider Electric Hungary

Melléklet(ek)
Add VMware vCenter Security Cert to PowerChute-keystore Manually.pdf [621.9 KB]
Add Vmware ESXi Host Security Certificate to PowerChute-keystore Manually.pdf [527.03 KB]