{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

What needs to be done to use Blokset at high altitudes (2000m, 3000m, etc.)?

It is possible to use BlokSeT at higher altitude >2000m. We have to apply the derating value as informed in the latest BlokSeT catalog.

As per the table below, derating to be applied for circuit breaker and rated voltage.

Altitude derating

Schneider Electric Indonesia

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: