Why does my ATS48 Soft Starter show PHF fault when stopping the motor?

Article available in these languages: Spanish

Issue:
ATS48 Soft Starter shows PHF fault when stopping the motor.

Product Line:
ATS48 soft starters

Environment:
All models, All serial numbers

Cause:
Information unavailable in current literature.

Resolution:
PHF is caused by too great of an imbalance in the current draw of the output phases.  If one phase is pulling considerably more or less current than the other two, PHF can occur.   PHF can also occur if one or more output phases are pulling no current (open phase).

Schneider Electric Indonesia

Why does my ATS48 Soft Starter show PHF fault when stopping the motor?

Article available in these languages: Spanish

Issue:
ATS48 Soft Starter shows PHF fault when stopping the motor.

Product Line:
ATS48 soft starters

Environment:
All models, All serial numbers

Cause:
Information unavailable in current literature.

Resolution:
PHF is caused by too great of an imbalance in the current draw of the output phases.  If one phase is pulling considerably more or less current than the other two, PHF can occur.   PHF can also occur if one or more output phases are pulling no current (open phase).

 

Schneider Electric Indonesia

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.