{}

Merek kami

Impact-Company-Logo-English Black-01-177x54

Selamat datang di Situs Web Schneider Electric

Selamat datang di situs web kami.

FAQ Pencarian

What is the maximum AIR (or SCCR) for the QMB/QMJ branch switches when used on a DC voltage system?

Issue:
Product Design Features

Product Line:
QMB branch switches

Resolution:
FIRST, VERIFY THAT THE SPECIFIC QMB/QMJ BRANCH SWITCHES HAVE A DC VOLTAGE RATING AND THIS SHOULD BE MARKED ON THE SWITCH WIRING DIAGRAM.


The maximum short circuit current rating for the QMB/QMJ branch switches when used on a DC voltage system is 10 kAIC. This applies to all DC voltage systems (see wiring diagram of switch to confirm if rated for DC; 250 Vdc maximum).

Schneider Electric Indonesia

Jelajahi lebih lanjut
Rentang:
QMB Fusible Power Distribution Panelboards
Jelajahi lebih lanjut
Rentang:
QMB Fusible Power Distribution Panelboards