{}

Merek kami

Impact-Company-Logo-English Black-01-177x54

Selamat datang di Situs Web Schneider Electric

Selamat datang di situs web kami.

FAQ Pencarian

Contactors fail to pass incoming inspection, contacts do not close.

Contactors should be tested under load, not with a digital meter. This is true even for devices that are in service.

See the attached paper.

Schneider Electric Indonesia

Lampiran

Ohmic verification of power contacts.docxOhmic verification of power contacts.docx [77.42 KB]
Jelajahi lebih lanjut
Rentang:
Lighting ContactorsTeSys K contactorsType S Multipole Lighting ContactorTeSys Deca contactorsTeSys F
Jelajahi lebih lanjut
Rentang:
Lighting ContactorsTeSys K contactorsType S Multipole Lighting ContactorTeSys Deca contactorsTeSys F