{}

Merek kami

Impact-Company-Logo-English Black-01-177x54

Selamat datang di Situs Web Schneider Electric

Selamat datang di situs web kami.
FAQ Pencarian
What would cause the error "Topological address index is not valid" in EcoStruxure Control Expert after a build?
Issue:
"Topological address index is not valid" error in EcoStruxure Control Expert after a build


Product Line:
EcoStruxure Control Expert


Resolution:
The error occur when a variable is assigned to a memory object that is not allocated in the processor configuration. In the example below, the variable has an array length of 26 EBOOLs starting at %M500 to %M525. The processor memory management is configured for only 512 Ebools(%M). This is not enough to satisfy the array length. To clear the error, simply increase the %M to a number greater than 525 and rebuild the project.


image

Schneider Electric Indonesia

Jelajahi lebih lanjut
Rentang:
Artikel yang mungkin berguna
Jelajahi lebih lanjut
Rentang: