{}

Merek kami

Impact-Company-Logo-English Black-01-177x54

Selamat datang di Situs Web Schneider Electric

Selamat datang di situs web kami.
FAQ Pencarian
Can MDGF be combined with ZSI when Ground Fault Alarm is selected using breakers with micrologic 5.0P or H or 5.0x LSI?
No .When GF alarm is selected in a double or multiple ended substation and when tie or ties breakers are present, short time function must be self restrained and since GF protection is not available in the trip unit . ZSI option must be deselected.

Schneider Electric Indonesia

Jelajahi lebih lanjut
Rentang:
Artikel yang mungkin berguna
Jelajahi lebih lanjut
Rentang: