Can a generator supply be connected to a SAIF feeder pillar manufactured to DEO (Works) specification?
Feeder pillars manufactured to DEO (Works) specification 039 can be fitted with an 800A generator way (i.e. 630A SAIF fuseway with non-removable fuse carriers fitted with solid copper links).
Please note, whilst the generator way can be retro-fitted it requires the space of at least 1 fuseway.