{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

What is the minimum MCset switchgear substation ceiling height?

MCset requires a minimum of 4 meter ceiling height from floor to ceiling to allow the safe dissipation of hot arc gasses.
For all MCset switchgear configurations more than 25kA or ceiling height less than 4m anti-arcing tunnel is needed.

For more information please see MCset Civil engineering guide on Schneider web page.

Schneider Electric Ireland

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: