Search FAQs
Contactor Selection table for DC current switching?
Guide for selection of contactor for DC application is in Attachment1.
E.g. for switching of 35A at 220VDC in utilization category DC-1 to DC-5 can be used contactor LC1D32 with 3 poles connected in series.
E.g. for switching of 35A at 220VDC in utilization category DC-1 to DC-5 can be used contactor LC1D32 with 3 poles connected in series.
Released for:Schneider Electric Ireland
Attachment(s)
Explore more
Range:
Explore more
Range: