Can an RCD be fitted onto the outgoing way of an Isobar and Acti9 Distribution Board?
The Isobar Distribution Boards outgoing ways are designed to be fitted only with iC60H MCB's up to and including 63A and RCBO's up to 45A
RCD's and other din rail devices cannot be fitted.
They should be fitted on a din rail.
- Incase of single phase boards, a multiservice single phase distribution board has a din rail already fitted.
- For a three phase board an extension box with a din rail of 17 single pole ways width is available.
Part number is SEA9BNEX034N for Acti9 Isobar distribution boards.
RCD's and other din rail devices cannot be fitted.
They should be fitted on a din rail.
- Incase of single phase boards, a multiservice single phase distribution board has a din rail already fitted.
- For a three phase board an extension box with a din rail of 17 single pole ways width is available.
Part number is SEA9BNEX034N for Acti9 Isobar distribution boards.
Released for:Schneider Electric Ireland