Sepam Series 80 information saving on power failure
The saving of information depends on whether or not the battery is present. In the event of a Sepam series 80 power failure, certain data will only be saved if the battery is present.
The data listed below are only saved if the battery is present:
- Peak demand current
- Peak demand active power
- Peak demand reactive power
- Tripping context
- Tripping current
- Disturbance recordings
- Starting current
- Starting time
- Alarm message history
- date and time
- Calculated active energy
- Calculated reactive energy
- Number of trips (phase overcurrent and earth fault)
- Machine heat rise
- Running hours counter and operating time
- Cumulative breaking current
- Number of operations
- Operating time
- Charging time
- Number of rackouts