Issue:
How is an ATS48 set up for basic programming?
Product line:
Altistart 48
Environment:
All models, all serial numbers
Cause:
Basic programming set up for the ATS48 soft starters.
Resolution:
SET menu:
IN= FLA motor amps
ACC= acceleration
STY= type of stop (f=freewheel, d=ramp stop, b=intel braking)
DEC= deceleration [only appears if Sty= d (ramp stop)]
ILT=current limit 400% or 4X your motor current is default value.
DRC menu:
CLP= Off (Torque Control). This is important if the ACC/DEC times have to be followed exactly.
Refer to the ATS48 User Manual for any further details.
The following video demonstrates this initial setup procedure:
How is an ATS48 set up for basic programming?
Product line:
Altistart 48
Environment:
All models, all serial numbers
Cause:
Basic programming set up for the ATS48 soft starters.
Resolution:
SET menu:
IN= FLA motor amps
ACC= acceleration
STY= type of stop (f=freewheel, d=ramp stop, b=intel braking)
DEC= deceleration [only appears if Sty= d (ramp stop)]
ILT=current limit 400% or 4X your motor current is default value.
DRC menu:
CLP= Off (Torque Control). This is important if the ACC/DEC times have to be followed exactly.
Refer to the ATS48 User Manual for any further details.
The following video demonstrates this initial setup procedure:
פורסם עבור: שניידר אלקטריק ישראל
Issue:
How is an ATS48 set up for basic programming?
Product line:
Altistart 48
Environment:
All models, all serial numbers
Cause:
Basic programming set up for the ATS48 soft starters.
Resolution:
SET menu:
IN= FLA motor amps
ACC= acceleration
STY= type of stop (f=freewheel, d=ramp stop, b=intel braking)
DEC= deceleration [only appears if Sty= d (ramp stop)]
ILT=current limit 400% or 4X your motor current is default value.
DRC menu:
CLP= Off (Torque Control). This is important if the ACC/DEC times have to be followed exactly.
Refer to the ATS48 User Manual for any further details.
The following video demonstrates this initial setup procedure:
How is an ATS48 set up for basic programming?
Product line:
Altistart 48
Environment:
All models, all serial numbers
Cause:
Basic programming set up for the ATS48 soft starters.
Resolution:
SET menu:
IN= FLA motor amps
ACC= acceleration
STY= type of stop (f=freewheel, d=ramp stop, b=intel braking)
DEC= deceleration [only appears if Sty= d (ramp stop)]
ILT=current limit 400% or 4X your motor current is default value.
DRC menu:
CLP= Off (Torque Control). This is important if the ACC/DEC times have to be followed exactly.
Refer to the ATS48 User Manual for any further details.
The following video demonstrates this initial setup procedure:
פורסם עבור: שניידר אלקטריק ישראל








זקוק לעזרה?
התחל כאן!
מצא תשובות כעת. חפש פתרון בעצמך או פנה אל אחד המומחים שלנו.
פניה למחלקת התמיכה
פנה לצוות שירות הלקוחות שלנו לקבלת מידע נוסף, תמיכה טכנית, סיוע בתלונות ועוד.
היכן לקנות?
אתר בקלות את מפיץ Schneider Electric הקרוב ביותר אליך.
גלוש ב'שאלות נפוצות'
עיין בשאלות הנפוצות לפי נושאים וקבל את התשובות שאתה מחפש.