The maximum number of devices that can be daisy chained out of the PowerLogic Network Interface Module (PNIM) RS-485 port are 32, without using repeaters. The maximum length of the daisy chain is dependent on the baud rate of the devices. See table below.
Typical maximum RS-485 Drive Distance
Baud Rate | 150-9600 | 19200 | 38400 | 57600 | 115200 |
Distance (feet) | 4000 | 3200 | 3000 | 2300 | 1600 |
Distance (meters) | 1220 | 975 | 914 | 701 | 488 |
*Note: Based on 24 AWG twisted shielded pair, 0.026 Ohm/ft (0.085 Ohm/m), 13pF/ft(41pF/m) conductor to conductor, 22 Pf/ft (72pF/m) conductor to shield.
פורסם עבור: שניידר אלקטריק ישראל
Product Line
PNIM
Environment
RS-485
Resolution
The maximum number of devices that can be daisy chained out of the PowerLogic Network Interface Module (PNIM) RS-485 port are 32, without using repeaters. The maximum length of the daisy chain is dependent on the baud rate of the devices. See table below.
Typical maximum RS-485 Drive Distance
Baud Rate | 150-9600 | 19200 | 38400 | 57600 | 115200 |
Distance (feet) | 4000 | 3200 | 3000 | 2300 | 1600 |
Distance (meters) | 1220 | 975 | 914 | 701 | 488 |
*Note: Based on 24 AWG twisted shielded pair, 0.026 Ohm/ft (0.085 Ohm/m), 13pF/ft(41pF/m) conductor to conductor, 22 Pf/ft (72pF/m) conductor to shield.
פורסם עבור: שניידר אלקטריק ישראל




















זקוק לעזרה?
התחל כאן!
מצא תשובות כעת. חפש פתרון בעצמך או פנה אל אחד המומחים שלנו.
פניה למחלקת התמיכה
פנה לצוות שירות הלקוחות שלנו לקבלת מידע נוסף, תמיכה טכנית, סיוע בתלונות ועוד.
היכן לקנות?
אתר בקלות את מפיץ Schneider Electric הקרוב ביותר אליך.
גלוש ב'שאלות נפוצות'
עיין בשאלות הנפוצות לפי נושאים וקבל את התשובות שאתה מחפש.