Issue:
When using the HMISTU and M241 PLC, is there a way to read the time information from the M241 PLC and use that to synchronize the HMISTU's internal clock?
Product Line:
Vijeo Designer, SoMachine, Magelis HMI, XBTGT, XBTGK, HMISTO, HMISTU, HMIGTO, HMIGTU, HMIGK
Resolution:
In order to synchronize the HMI time with the M241 time, you must make use of a few libraries in SoMachine.
You will need to use the following:
SysTimeRtcGet -> This gets the controller's time
SysTimeRtcConvertUtcToDate -> This will convert the controller's UTC info to a readable date
SYSTIMEDATE -> This will store all the date and time information in tags that can be used by the HMI in Vijeo Designer.
For a complete setup of an example of how to get and set the PLC time, please see the example in the attached file.
When using the HMISTU and M241 PLC, is there a way to read the time information from the M241 PLC and use that to synchronize the HMISTU's internal clock?
Product Line:
Vijeo Designer, SoMachine, Magelis HMI, XBTGT, XBTGK, HMISTO, HMISTU, HMIGTO, HMIGTU, HMIGK
Resolution:
In order to synchronize the HMI time with the M241 time, you must make use of a few libraries in SoMachine.
You will need to use the following:
SysTimeRtcGet -> This gets the controller's time
SysTimeRtcConvertUtcToDate -> This will convert the controller's UTC info to a readable date
SYSTIMEDATE -> This will store all the date and time information in tags that can be used by the HMI in Vijeo Designer.
For a complete setup of an example of how to get and set the PLC time, please see the example in the attached file.
פורסם עבור: שניידר אלקטריק ישראל
Issue:
When using the HMISTU and M241 PLC, is there a way to read the time information from the M241 PLC and use that to synchronize the HMISTU's internal clock?
Product Line:
Vijeo Designer, SoMachine, Magelis HMI, XBTGT, XBTGK, HMISTO, HMISTU, HMIGTO, HMIGTU, HMIGK
Resolution:
In order to synchronize the HMI time with the M241 time, you must make use of a few libraries in SoMachine.
You will need to use the following:
SysTimeRtcGet -> This gets the controller's time
SysTimeRtcConvertUtcToDate -> This will convert the controller's UTC info to a readable date
SYSTIMEDATE -> This will store all the date and time information in tags that can be used by the HMI in Vijeo Designer.
For a complete setup of an example of how to get and set the PLC time, please see the example in the attached file.
When using the HMISTU and M241 PLC, is there a way to read the time information from the M241 PLC and use that to synchronize the HMISTU's internal clock?
Product Line:
Vijeo Designer, SoMachine, Magelis HMI, XBTGT, XBTGK, HMISTO, HMISTU, HMIGTO, HMIGTU, HMIGK
Resolution:
In order to synchronize the HMI time with the M241 time, you must make use of a few libraries in SoMachine.
You will need to use the following:
SysTimeRtcGet -> This gets the controller's time
SysTimeRtcConvertUtcToDate -> This will convert the controller's UTC info to a readable date
SYSTIMEDATE -> This will store all the date and time information in tags that can be used by the HMI in Vijeo Designer.
For a complete setup of an example of how to get and set the PLC time, please see the example in the attached file.
פורסם עבור: שניידר אלקטריק ישראל




זקוק לעזרה?
התחל כאן!
מצא תשובות כעת. חפש פתרון בעצמך או פנה אל אחד המומחים שלנו.
פניה למחלקת התמיכה
פנה לצוות שירות הלקוחות שלנו לקבלת מידע נוסף, תמיכה טכנית, סיוע בתלונות ועוד.
היכן לקנות?
אתר בקלות את מפיץ Schneider Electric הקרוב ביותר אליך.
גלוש ב'שאלות נפוצות'
עיין בשאלות הנפוצות לפי נושאים וקבל את התשובות שאתה מחפש.