{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

How to transfer the application program from Primary to Standby PLC automatically in Quantum Hot Standby System.

Sense the Status word bit %SW61.4 for program mismatch in both controllers. When true make %SW60.5 high for
program transfer from primary to standby PLC.

QUANTUM.PNG

Schneider Electric India

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: