{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

What is the mathematical equation for long time protection curves for protection units on Compact NS /NSX breakers.

The mathematical equation is I²t = constant.

And generally the time tripping is given at 6 Ir.

For example the Micrologic 2 for NSX gives the tripping time 16s at 6Ir.
Then what’s about time tripping at 2Ir?
I²t = I’²t’
t = (6/2)² x 16 = 144 s

This mathematical relationship is available only in long time delay of course when you reach
the Isd (short circuit) threshold it is no longer available.

Schneider Electric India

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: